Product code | C1-004SFC |
Power voltage | 1 phase: 200V-15% to 240V +10% |
Output voltage | 3 Phase 220-240VAC |
Rated output current | 3.0A |
Power supply frequency | 50/60 Hz fluctuation amplitude ± 5% |
Wattage | 400W |
Overload capacity | 150% 60 seconds |
Starting torque | 200% at 0.5Hz (sensorless vector control) |
Carrier frequency range | 2kHz-15kHz |
Setting frequency range | 0.1Hz-400Hz |
Input frequency resolution | Digital : ± 0.01% of maximum frequency Analogue: ±0.2% of maximum frequency (25°C ±10°C) |
Display | 7-segment LED (5 digits) |
Acceleration and deceleration time | 0.1-3600 seconds |
Frequency Settings | Control panel: set value by keyboard, internal resistor External signal: 0 to 10 VDC (input impedance 10kΩ), 4 to 20mA (input impedance 100Ω), Potentiometer (1k to 2kΩ, 2W) Communication: RS485 ModBus RTU, other network options |
Runs FWD/REV | Control panel: Run / Stop (Forward / Reverse changes by command) External signal: Forward run/stop, Reverse run/stop Communications: RS485 ModBus RTU, other network options Terminals : 7 terminals, source/sink can be changed with a short bar |
Other functions | V/f control, manual/automatic torque boost, output voltage gain adjustment, AVR function, starting voltage reduction, motor data selection, auto tuning, stability control motor timing, reverse run protection, simple position control, simple torque control, torque limit, automatic carrier frequency reduction, energy saving operation, PID function , non-stop operation upon instantaneous power failure, brake control, DC injection brake, dynamic brake (BRD), upper and lower frequency limits, frequency hopping, gain and decel curve (S, U , U inversion , EL-S), 16-stage speed configuration, fine adjustment of start frequency, stop speed increase and decrease, jog process, frequency calculation, frequency addition, 2 speed increase/decrease phase, stop mode selection, start/stop frequency, analog input filter, window comparator, input input response time, output signal delay/hold function , rotation direction restriction, stop key selection, software lock, safety stop function, scaling function, display restriction, function password, user parameters, initialization, initial display selection , cooling fan control, alarm, trip retry, pull-in frequency reset, frequency matching, overload limit, overcurrent limit, AVR DC bus voltage |
Input functions | FW (forward command), RV (reverse command), CF1 - CF4 (multi-stage speed setting), JG (fast command), DB (external brake), SET (second motor set), 2CH (2-stage acceleration / decel. command), FRS (free running stop command), EXT (external trip), USP (start function), CS (commercial power switching), SFT (soft lock ), AT (analog input selection), RS (reset), PTC (thermistor protection), STA (start), STP (stop), F/R (forward/reverse), PID ( PID off), PIDC (PID reset), UP (remote control function), DWN (remote control down function), UDC (remote control data clear), OPE (operator control ), SF1 - SF7 (multi-stage speed setting; bit operation), OLR (overload limit), TL (torque limit on), TRQ1 (torque limit switch1), TRQ2 (torque limit switch2), BOK (brake acknowledge), LAC (LAD cancel), PCLR (position clearance), ADD (frequency extra enable), F-TM (force connector mode), ATR (enable torque command input), KHC (Clear accumulated power), MI1 - MI7 (general purpose input for EzSQ), AHD (analog command hold), CP1– CP3 (multistage position switch), ORL (zero return signal limit), ORG (zero return trigger signal), SPD (speed/position switching), GS1, GS2 (STO input , safety related signal), 485 (start communication signal), PRG (execute EzSQ program), HLD (hold output frequency), ROK (run command enable), EB (transmit shows rotation direction of phase B), DISP (display limit), NO (no function) |
Output functions | RUN (run signal), FA1 - FA5 (frequency arrival signal), OL, OL2 (overload pre-notification signal), OD (PID deviation error signal), AL (warning signal), OTQ ( over/under torque threshold), UV (under voltage), TRQ (torque limit signal), RNT (run time out), ONT (power ON time out), THM (warning heat), BRK (brake release), BER (brake error), ZS (0Hz detection), DSE (excessive speed deviation), POK (positioning completed), ODc (analog voltage input disconnect ), OIDc (analog current input disconnect), FBV (second stage PID output), NDc (network disconnect detection), LOG1 –LOG3 (Output signal logic), WAC (warning capacitor life), WAF (cooling fan warning), FR (start contact), OHF (heatsink overheat warning), LOC (Low Load), MO1 - MO3 (common output for EzSQ), IRDY (inverter ready), FWR (forward active), RVR (reverse active), MJA (major error),WCO (window comparator O), WCOI (window comparator OI), FREF ( frequency command source), REF (run command source), SETM (second motor idle), EDM (STO (safe torque off) performance monitoring), OP (control signal options ), NO (no function) |
Protection function | Overcurrent, overvoltage, undervoltage, overload, brake resistor overload, CPU error, memory error, external trip, USP error, power-on ground error detected, temperature error, communication error internal, driver error, thermistor error, brake error, safety stop, low speed overload, modbus communication error, option error, encoder disconnection, overspeed, EzSQ command error , EzSQ loop error, EzSQ execution error, |
Ambient temperature | -10 ℃-50 ℃ |
Humidity | 20-90% RH, non-condensing |
Storage temperatures | -20℃- +65℃ |
Standard | IP20 |