Hanyoung's GE6-P61A counters and timers are indispensable devices in industrial automation systems. With the ability to provide precise time measurement and control solutions, this product helps improve production efficiency and ensure smooth operation in many different industries. In this article, we will delve into the GE6-P61A installation process, from initial preparation to detailed implementation steps. Understanding how to install and use counters / timers not only helps optimize the device's features, but also contributes to extending its life and minimizing risks during operation.1. General introduction of Counter / Timer GE6-P61A
• Product: Counter / Timer GE6-P61A
• Series: GE (Discontinued) --> Replacement product line: LC series
• Display: 6 characters, allowing easy and accurate monitoring.
• Supply voltage: 100~240VAC, suitable for most electrical systems.
• Signal input: Compatible with NPN non-voltage input and PNP voltage input, ensuring flexibility in connection.
• Control output: Including 1NO Relay and 1NO + Batch Relay, providing a variety of control options.
• Connection type: Screw-in, ensuring a firm connection and easy installation.
• Dimensions: 72x36x86mm, compact design suitable for limited spaces.
The Hanyoung GE6-P61A Counter/Timer is an ideal choice for industrial applications, providing high efficiency and reliability for automation systems.2. Specifications of GE6-P61A
Parameter
Product code | GE6-P61A |
Power supply voltage | 100 - 240 VAC 50 – 60Hz |
Power consumption | Approx. 13.5VA (100 - 240 VAC), Approx. 5W (24 - 60 VDC), Approx. 9 VA (24 - 60 VAC) |
Character height (mm) | 11 (count value), 8 (set value) |
Input counting speed | 1 cps, 30 cps, 1 kcps, 10 kcps (ON/OFF ratio: 1:1, "H" level: 5 - 3 VDC, "L" level : 0 - 2 VDC) |
Data storage | 10 years |
Input | CP1, CP2, RESET, BATCH RESET (excluding TOTAL) Level [H]: 4 - 30 VDC, Level [L]: 0 - 2 VDC, internal pull-up resistor for NPN/PNP connection |
Minimum input signal | Counter | Minimum external reset input signal: within 0.1ms, 1ms, 20ms |
Timer | Minimum START, INHIBIT, RESET input signal: select 1 ms, 20 ms |
External power supply | Max 12 V d.c 100 mA |
One-shot output | 0.01 - 99.99 s [OUT1, OUT2(OUT)] |
Control output | Mechanical contact | Level 1 | 1a (OUT) |
Level 2 | 1a (OUT1), 1c (OUT2) |
Capacity | contact a: 250 VAC 3 A (resistive load), contact b: 250 VAC 2 A |
Transistor contacts | Level 1 | 2 NPN contacts (OUT, BAT.O) |
Level 2 | None |
Capacity | Open collector, 30 VDC, 100 mA max. |
Timer operation error | When power on: Max ±0.01% ±0.05 seconds When reset: Max ±0.005% ±0.003 seconds |
Isolation impedance | Minimum 100 ㏁ (500 VDC) between live and non-live parts. |
Electrical strength | 2000 V a.c 60 Hz for about 1 minute (different polarities) |
Noise resistant | Square wave by noise simulator (1us pulse every 16ms) ±2kV (source terminal), ±500 V (input terminal) |
Vibration resistant | 10 - 55 Hz, peak intensity 0.5mm, 3 axes each way about 2 hours |
Shock resistance | 300 m/s2, 3 axes 3 times |
Relay Life | Electricity | Minimum 100 thousand times (250 VAC 2 A load resistance) |
Mechanical | Minimum 1 million times |
Protective structure | IP65 (front only) |
Storage temperature | -20 oC ~ 65 oC |
Environmental temperature and humidity | -10 oC ~ 55 oC, 35% ~ 85% RH |
Weight | 138g |
Code and size selection table
Advantage
• Counter or timer function optional.
• High speed counter.
• 1 shot output.
• 12 kinds of input modes.
• 12 kinds of start time range3. Detailed GE6-P61A installation instructions
INPUT MODEOUTPUT MODEVí dụ: Use GE6-P61A to count products
• Use encoder HE50B-8-100-3-T-24 to count pulses (replace for products)
• 12 pulses (12 products) = 1 BATCH (1 batch)
Setting:- • Press and hold 2 seconds (can be pressed to find the desired mode)
• Appear press
• Appear choose press
• Appear choose press
• Appear choose 01.00 (s) press
• Appear choose press
• Appear choose press
• Appear choose press
• Appear choose 0.01000 press
• Appear choose press
• Appear choose press
• Appear choose press …
• Appear choose press …
• Appear choose press …
- Return to home screen to continue installation
• Press Hold for 2 seconds until you see one of the SET or BAT LEDs light up.
• Use move up and down 2 setting functions
• If the SET led lights up first, press to move to tens and units and press to adjust to value 12 (pulse/product) then press
• Press leave the BAT LED on to set the initial value = 0 then press (can be pressed if previous value is different from 0)
- • Press When both SET and BAT LEDs are on, you can start counting
- Note:
- • When using relative encoder, it is recommended to use the function or and adjust the input signal both the hardware on the control box body and the settings.
- • Use to move to the desired parameter value.
- • Use to increase the value from 0-9 or to change the function of the mode , parameter
• depends on the maximum resolution of the encoder.
4. GE6-P61A Counter/Timer Installation Guide Video
Conclusion
In case you need to learn more or need technical advice, please contact Amazen immediately via:
Hotline: 0934 399 068 - Sales: 0938 072 058
Email: amazen@amazen.com.vn
With a team of highly specialized technical support and sales consultants, our company is confident that it will bring customers the best shopping experience. Amazen commits that all inverter products we currently provide are genuine, 100% new, guaranteed quality and fully accompanied by CO/CQ and VAT certificates.