View: 0

Installation instructions for FOX-2006 temperature controller

To help you have the most detailed overview of how to connect and set the temperature of FOX-2006. Amazen will choose the FOX-2006 temperature controller to combine with other devices to create a complete system. To complete a complete system, we will need other supporting devices:
- In order to ensure safe operation of the system, it is necessary to use an additional MCB switch (LS BKJ63N 2P 16A) to protect the devices in the system when overloaded and short circuited. .
- The input device is a pair of NTC temperature sensors.
- The output of the FOX-2006 temperature controller is a relay output with a voltage level of 250VAC - 2A, so it is necessary to use an alarm/actuator device (HANYOUNG CRP-25AG & CRP-25AR Indicator Light) with power. Voltage is 220VAC.

1. Select devices combined with FOX-2006

Switchgear BKJ63N 2P 16A

With the feature of automatically cutting off power when there is an overload or problem in the electrical system, helping to protect the safety of equipment and users, we choose BKJ63N 2P 16A to protect the system.
Advantage:
•    Made from high quality materials, ensuring high durability and reliability.
•    Easy to install and use, saving time and effort in the installation and maintenance process.
•    Power cutting capacity up to 6kA, meeting the needs of use in many industrial and civil environments.
•    Reliable and stable in preventing the risk of short circuits, helping to avoid fire situations and electrical accidents.
However, the sensitivity of Aptomat MCB BKJ2P 16A 6kA LS may not be suitable for some specific environments and devices. So you can choose another switchgear that is more suitable for your electrical system.
•    Only protects one phase, does not protect against possible faults on another phase.
•    Sometimes unwanted circuit shocks or power cuts may occur due to the sensitivity of the circuit breaker.
Thiết bị đóng cắt LS BKJ63N 2P 16A
See more technical specifications of BKJ63N 2P 16A at: https://amazen.com.vn/cb-tep-mcb-ls-bkj63n-2p-16a-6ka.html

Hanyoung CRP-25AG & CRP-25AR indicator lights

•    Hanyoung CRP series indicator lights have a power voltage of 100-240VAC.
•    Max consumption current. 4.4VA can be best stored at temperatures from -40-60℃ (suitable under normal conditions).
•    CRP works well and consumes little energy.
Specifications

Product name

Hanyoung indicator lights

Series

CRP

Power voltage

100-240 VAC

Consumption stream

Max.4.4VA

Installation hole

Ø25

Color

Green (CRP-25AG), Red (CRP-25AR).

Protection level

IP65

Domino HYT-204

The product is made from fireproof ABS plastic. Plated contacts help prevent oxidation.

Domino HYT-204

Buy Domino Hanyoung HYT-204 at: https://amazen.com.vn/domino-hanyoung-hyt-204.html

•    Dimensions: 20 x 30 x 68 mm
•    Rated voltage: 600V
•    Working environment temperature: -20 ~ 55 degrees Celsius
•    Working environment humidity: 45 – 85% R.H

2. Introducing the FOX-2006 temperature controller

FOX-2006 temperature controller is a device manufactured by Conotec Korea, used to adjust and maintain temperature in heating, cooling systems or other industrial applications.
Characteristic:
•    Temperature measuring range: -55.0°C to 99.9°C
•    Accuracy: ±0.1°C
•    Sensor type: NTC (includes 2 3 meter long NTC sensors)
•    Control type: Relay ON/OFF
•    Function:
 o    Displays current temperature and set temperature
 o    Horn warning function when temperature exceeds or falls below set value
 o    Auto tuning function (PID)
 o    Keypad lock function
•    Dimensions: 77(W) x 35(H) x 80(D)
•    Cutting hole size: 71(W) x 29(H)
•    Power source: 220-230VAC 50/60Hz (or 12V, 24V AC/DC optional)
Advantage:
•    Easy to use and install
•    Reasonable price
•    High precision
•    Stable operation
•    Integrate many functions
Application:
•    Indoor heating and cooling system
•    Freezer, refrigerator
•    Egg incubator
•    3D printer
•    Mist spray system
•    And many other industrial applications

Điều khiển nhiệt độ FOX-2006

See more information about FOX-2006 at: Amazen industrial electrical equipment

3. Steps to install FOX-2006 temperature controller

Checking devices

Check the temperature controller and make sure it has not been damaged during transportation

Connect the power cord

FOX-2006 connection diagram

Sơ đồ đấu nối dây FOX-2006

Set parameters

Temperature, threshold and corresponding value

Các chế độ cài đặt và ngưỡng nhiệt

Set temperature settings for the controller

Cài đặt nhiệt độ Bộ điều khiển nhiệt độ FOX-2006

The screen displays the current temperature value
•     Press the "Set" key and the setting value will flash on the display.
•     Switch to “Output 1 temperature adjustment” mode.
•     Press the "Set" key.
•     Press the "Setting up" or "Setting down" key to change the output temperature value 1.
•     Press the "Set" key.
•     Switch to “Output 2 temperature adjustment” mode.
•     Press the "Set" key.
•     Press the "Setting up" or "Setting down" key to change the output temperature value 2.
•     Hold down the "Set" key for 2 seconds.
•     The setting value will be saved and the current temperature will be displayed at the same time.

Cài đặt các thông số nhiệt cảnh báo FOX-2006

•      Press and hold the "Set" key for 5 seconds
•      The temperature value flashes on the display screen
If you press the "Increase" key, switch to program 2, or program 3
Press the "Reduce" key to return to the previous program.
If pressing "Set" key switches to HSP mode (maximum temperature limit setting)
•      Press the "Set" key
•      Press the "increase" key  up to 99.9 degrees Celsius or press the "decrease" key to switch to LSP mode (minimum temperature limit setting)
•      Press the "Set" key
•      Press the "Increase" key to return to HSP mode (maximum temperature limit setting) or press the "Decrease" key to min -55.0 degrees Celsius
•      Press the "Set" key
•      Switch to “temperature adjustment of sensor S1” mode
•      Press the "Set" key
•      Press the "Increase" key or press the "Decrease" key 10.0~-10.0 degrees Celsius
•      Press the "Set" key
•      Switch to “S2 sensor temperature adjustment” mode
•      Press the "Set" key
•      Press the "Increase" key or press the "Decrease" key 10.0~-10.0 degrees Celsius
•      Press the "Set" key
•      Switch to “Number of temperature display channels” mode
•      Press the "Set" key
•      Press the "Increase" key or press the "Decrease" key only S1 (1), only S2 (2), S1 and S2 (3)
•      Press the "Set" key
•      Switch to “Lock function” mode
•      Press the "Set" key
•      Press the "Increase" key (3) on or press the "Decrease" key (5) off
•      Press the "Set" key to return to program 1
                                                 ------------------------------------------------------------------------------
•      Press the "Increase" key to switch to program 2
•      Press the "Set" key
•      Switch to “Output function selection 1” mode
•      Press the "Set" key
•      Press "Increase" key H (heating) or press "Decrease" key C (cooling)
•      Press the "Set" key
•      Switch to “Output Time Delay 1” mode
•      Press the "Increase" key or press the "Decrease" key 190~0 minutes
•      Press the "Set" key
•      Switch to “Temperature error setting” mode
•      Press the "Increase" key or press the "Decrease" key 25.0~0.1 degrees Celsius
•      Press the "Set" key
•      Switch to “Output function selection 2” mode
•      Press the "Set" key
•      Press "Increase" key H (heating) or press "Decrease" key C (cooling)
•      Press the "Set" key
•      Switch to “Output time delay 2” mode
•      Press the "Increase" key or press the "Decrease" key 190~0 minutes
•      Press the "Set" key to return to program 2
                                              ------------------------------------------------------------------------------
•      Press the "Increase" key to switch to program 2
•      Press the "Set" key
•      Switch to “Output function selection 1” mode
•      Press the "Set" key
•      Press "Increase" key H (heating) or press "Decrease" key C (cooling)
•      Press the "Set" key
•      Switch to “Output Time Delay 1” mode
•      Press the "Increase" key or press the "Decrease" key 190~0 minutes
•      Press the "Set" key
•      Switch to “Temperature error setting” mode
•      Press the "Increase" key or press the "Decrease" key 25.0~0.1 degrees Celsius
•      Press the "Set" key
•      Switch to “Output function selection 2” mode
•      Press the "Set" key
•      Press "Increase" key H (heating) or press "Decrease" key C (cooling)
•      Press the "Set" key
•      Switch to “Output time delay 2” mode
•      Press the "Increase" key or press the "Decrease" key 190~0 minutes
•      Press the "Set" key to return to program 2
Note: after 2 seconds of not pressing any key, it will automatically return to the temperature display.

4. Detailed video installation instructions for FOX-2006

In case you need to learn, need technical advice and order FOX-2006 products, please contact Amazen immediately via:
Hotline: 0934 399 068 - Sales: 0938 072 058
Email: amazen@amazen.com.vn

With a team of highly specialized technical support and sales consultants, our company is confident that it will bring customers the best purchasing experience.
Amazen commits that all inverter products we currently provide are genuine, 100% new, quality guaranteed and fully accompanied by CO/CQ and VAT certification documents.