Product information of Overload relays LS MT400
General information of Overload relays LS MT400
Overload relay MT LS has 3 poles, specialized for contactors of LS MC series. Compact size, smart design, easy to install, install in many difficult locations, affordable price.
Specifications Overload relays LS MT400
Frame size | 400AF |
Trip class | 10A | 20 |
Type | Non-differential(3P-2 heater) | MT400/2H□S | - |
Non-differential(3P-3 heater) | MT-400/3H□S | - |
Differential type | MT-400/3K□S | MT-400/3D□S |
Terminal type | Screw clamp |
Number of poles | 3 |
Rated operational voltage (Ue) | 690V |
Rated insulation voltage (Ui) | Up to 690V |
Rated impulse voltage (Uimp) | 6kV |
Degree of protection (IEC 60 529) | IP 20 |
Temperature compensation (C) | -5~+40℃ |
Functions | Trip indicating | ■ |
Stop | ■ |
Test | ■ |
Manual/Automatic Reset | ■ |
Setting range(A) | 85~400A |
Nominal current rating | Wire size | | |
mm2 | AWG |
107 | 50 | 1 | 85~125 |
113 | 50 | 1 | - |
130 | 50 | 0 | - |
130 | 70 | 0 | 100~160 |
153 | 95 | 0 | 120~185 |
200 | 120 | 250 | 160~240 |
265 | 185 | 350 | 200~330 |
350 | 240 | 500 | 260~400 |
Applied contactors | MC-130a, 150a |
Dimension of Overload relays LS MT400
Weight: 2.6kg
Use of Overload relays LS MT series
Overload relay LS is an auxiliary electrical device used to protect motors and circuits from overload, with a 3-pole thermal bimetal structure. When a fault is detected, it will automatically disconnect the power circuit to protect the load, the process to perform takes time from a few seconds to a few minutes of impact. In addition, the thermal relay does not automatically trip in the event of a short circuit.
Advantage of Overload relays LS MT series
- Compact design saves space.
- Anti-fingerprint design.
- World class products according to IEC and UL standards.
- Environmentally friendly products: comply with the Safe Electronic Equipment Standard RoHS rule.