The DriveView9 software user manual for controlling the LS SV0022IS7-4NO inverter provides a simple and efficient process for setting up and optimizing motor performance. The software allows users to configure control parameters such as speed, frequency, and operating mode through an intuitive interface. To get started, users need to connect the inverter to a computer via an RS485/USB converter, then install DriveView9 and perform the necessary configuration steps. With monitoring and fault diagnosis features, DriveView9 helps users monitor the inverter's operating performance, thereby improving the efficiency and reliability of the control system.
I. Choose items for systems
LS SV0022IS7-4NO inverter can be combined with devices and software to control the motor to operate at the desired speed as well as run at multiple speeds. The system should be controlled by a rotary switch to select speed levels differenations, or use a potentiometer to adjust the speed flexibly and accurately. This combination helps to optimize the motor's performance, meeting many different requirements in industrial applications.
1. LS SV0022IS7-4NO inventer
1.1. The overview about LS SV0022IS7-4NO
The LS iS7 SV0022iS7-4NO inverter operates with a 3P 380V voltage and a capacity of 2.2kW, belonging to the iS7 product line, specially designed for heavy-duty applications. This product is upgraded with many powerful and advanced functions, helping to optimize performance and meet industrial needs well. The interface of the inverter is very user-friendly, making it easy to install and adjust. With a wide power range of up to 375kW and high torque, this 3-phase inverter ensures optimal working performance. In addition, users can choose from a variety of measurement units on the LCD screen, including watts (W), amps (A), milliamps (mA), volts (V), and many other parameters, helping to monitor and control the operation of the device accurately.
Hình I-1 INVENTER LS SV0022IS7-4NO
1.2. The technical specification LS SV0022IS7-4NO inventer
Specification | |
Input specification | |
Voltage | 3 phase 380~480V ±10% |
Frequency | 50/60Hz ±5% |
Output specification | |
Power | 2.2kW |
Voltage rate
| 6A |
Output frequency | 0-400Hz |
Voltage | 3 phase 380V |
Basic general specification | |
Control | V/F or Sensorless vector |
Overload capacity | 150% in 1 min |
Input analog signals | 0~10V, -10~10V, 0~20mA |
Input option signal | NPN/PNP |
Basic protection | Overvoltage, undervoltage, overload, inverter overheating, motor overheating, ground fault, output phase loss, speed loss, hardware fault, fan fault |
Working_ambient_temp | -10℃ ~ 50℃ |
Inventory temp | -20℃ ~ 65℃ |
Protection levels | IP 20, NEMA1 (Temp 40℃) |
Weight | 0.77 KG |
1.3. Instruction information code LS SV0022IS7-4NO
Hình I-2 ODERING INFORMATION LS SV0022IS7-4NO
1.4. The dimension of LS SV0022IS7-4NO inventer
Hình I-3 DIMENSION OF LS SV0022IS7-4NO
1.5. The connection map for LS SV0022IS7-4NO inventer
2. Control screen SV-IS7-LCD-LOADER
2.1. The overview about SV-IS7-LCD-LOADER
Used to set, monitor parameters, and control IS7 series inverter functions. Can be used as a separate screen to help pull the inverter screen out to the cabinet or control the inverter far from the installation location.
Hình I-4 CONTROL SCREEN IS7-LCD-LOADER
2.2. The functions button of SV-IS7-LCD-LOADER
Hình I-4 Control screen IS7-LCD-LOADER
2.3. The dimension of SV-IS7-LCD-LOADER
Hình I-6 DIMENSION OF SV-IS7-LCD-LOADER
3. Tranfer route RS485-USB
3.1. Introduce overview about RS485-USB
The RS485-USB communication converter converts signals from the computer's USB standard to asynchronous RS485 standard at high speed, allowing flexible connection between the computer and devices using the RS485 protocol.
Hình I-7 SINGNAL TRANFER ROUTE RS485-USB
3.2. Technical specification RS485-USB
Supported operating systems:Compatible communication standards: USB 2.0 | Windows XP, Vista, Windows 7, Linux, MacOS và WinCE 5.0 |
Compatible communication standards | USB 2.0 |
Speed range baud | 75 – 115200 bps |
Maximum distance | 1200m |
Directly powered | from usb that shouldn't be supported for outside output |
Working ambient_temp | 40 –> 80 |
Dimension | 6.1 x 1.6 x 1.3cm |
Hình I-8 ODERING INFORMATION MRF-A3A2
4. DOMINO 4P 20A HANYOUNG
4.1. Introduce overview about DOMINO 4P 20A HANYOUNG
This product is made from ABS plastic that can prevent burning, Plated contacts help prevent oxidation.
Hình I-10 OMINO 4P 20A HANYOUNG
4.2. The dimension of 4P 20A HANYOUNG
- Dimension: 20 x 30 x 68 mm
- Voltage rate: 600V
- Working ambient temp: -20 ~ 55 degree C
- Working ambient humi: 45 – 85% R.H
5. MCB LS BKJ63N-2P-16A
5.1. The introduce overview about MCB LS BKJ63N-2P-16A
LS BKJ63N MCB switching device is compactly designed, has 2 phases, rated current 16A, short-circuit breaking current 6kA, short-circuit withstand current 6kA, meets IEC 60947-2; IEC/EN 60898-1 standards.
Hình I-11 MCB LS BKJ63N
5.2. The technical specification MCB LS BKJ63N-2P-16A
Hình I-12 TECHNICAL SPECIFICATION MCB LS BKJ63N
5.3. The dimension of MCB LS BKJ63N-2P-16A
Hình I-13 DIMENSION MCB BKJ63N
5.4. Advantage and disadvantage MCB LS BKJ63N-2P-16A
- Advantage of MCB LS BKJ63N-2P-16A
This device can automatically cut off the power when overload or failure occurs, protecting the safety of the device and the user. With high-quality materials, the product ensures outstanding durability and reliability. Easy installation and use help save time and effort. The power cut-off capacity is up to 6kA, suitable for many industrial and civil environments, and is reliable in preventing electrical short circuits, minimizing the risk of fire and accidents.
- Disadvantage of MCB LS BKJ63N-2P-16ASometimes, unexpected shocks or power cuts may occur due to the sensitivity of the Circuit Breaker
The LS MCB BKJ2P 16A 6kA Circuit Breaker may have some limitations, including a sensitivity that is not suitable for some specific environments and equipment. This product is more expensive than similar options on the market and only protects one phase, not fully protecting against faults on other phases. Sometimes, due to the high sensitivity, unexpected shocks or power cuts may occur.
5.5. MCB LS BKJ63N-2P-16A in deployment fields
Mainly used in civil power grids and distribution cabinets, such as lighting cabinets and socket supply cabinets. This product is very suitable for buildings, high-rise buildings, apartments, offices, as well as private homes, helping to ensure the safety and efficiency of the electrical system.
II. DRIVEVIEW9 apps
DriveView-9 is the latest software from LS, supporting parameter setting and configuration for inverter series such as C100, G100, H100, M100, S100, iG5A, ip5A, iS7, iV5 and iV5L. With an intuitive interface and compact capacity, DriveView-9 helps engineers easily set up, detect errors and handle them quickly, improving configuration efficiency and saving time.
III. Inverter connection diagram using converter RS485-USB
RS485-USB Hình II-1 Inverter connection diagram using converter RS485-USB
IV. The advantage and disadvantage LS SV0022IS7-4NO
1. Advantage LS SV0022IS7-4NO
The inverter has many flexible control functions, along with diverse signal input and output options. It supports the integration of many expansion modules, ensuring high durability and easy installation, meeting the requirements of industrial applications.
2. Disadvantage LS SV0022IS7-4NO
The inverter has a fairly high investment cost and requires the purchase of an additional LCD control screen, because the device is not equipped with this screen, causing additional costs for the user.
V. LS SV0022IS7-4NO inventer speed controllation in deployment fields
Frequency converters are increasingly widely used in speed control for machinery in many fields, especially in industry and construction. They are effectively used for equipment such as: crushers, rolling mills, tractors, coating machines, fiber machines, plastic machines, rubber, paint, chemicals, textiles, dyeing, packaging, wood processing, conveyor belts, cranes, cooling towers, lifting equipment, air compressors, as well as pumps and fans. Thanks to frequency converters, the performance of machinery is optimized, contributing to energy savings and improved production efficiency.
VI. Video tutorial on using Driveview9 software to control the speed of the inverter LS-SV0022IS7-4NO
Conclusion
In case you need to learn more or need technical advice, please contact Amazen immediately via:
Hotline: 0934 399 068 - Sales: 0938 072 058